beautypg.com

Rockwell Automation AADvance Controller Safety Manual User Manual

Page 85

background image


Document: 553630
ICSTT-RM446K-EN-P Issue: 10

_C

4-29

When the safety accuracy between channels exceeds the following limits then
a discrepancy alarm is set for the input channel

Digital Input Module = 8%

Analogue Input Module = 2%

In both situations the following safe values are reported by the variables:
Digital input modules

Input state FALSE

Line fault TRUE

Discrepancy TRUE

Channel fault TRUE

and the voltage value is 0mV
Analogue input module

process value = a calculated value based on a count value of 0 (51 counts =

0.2mA)

line fault TRUE

Discrepancy TRUE

Channel Fault TRUE

Count value 0

In safety critical applications, the discrepancy alarms shall be

monitored by the application program and be used to provide an alarm to the
plant operations personnel.

Output Module Safety Functions

Digital Output Module Safety Functions

The digital output module is rated at SIL3 as a fail-safe module. In dual

redundant configurations it can be used for energize to action and de-energize
to trip SIL3 applications. Each module provides the following safety functions:

output channel signals based on commands from the processor.

redundant voltage and current measurements to the processor modules

for monitoring and diagnostics.

over current and over voltage channel protection.

executing diagnostic tests (on command from the processor module) and

reporting results back to the processor module.

On power up or module insertion all output channels are set to the de-

energized (fail-safe) state until command states are received from the

processor. Each channel is driven individually according to the command

state values.

When the module is unlocked, all of its output channels (including any

channels set to hold last state) always go to the de-energized state.

the module enters a Shutdown Mode when the time between processor

commands exceeds the PST.