beautypg.com

Rockwell Automation AADvance Controller Safety Manual User Manual

Page 112

background image

5-4

Document: 553630

ICSTT-RM446K-EN-P Issue: 10

_C

Safety Manual (AADvance Controller)


Description

Yes/No

Do safety related inputs and outputs use only those configurations
identified as safety related ?

Are there any safety-related, normally de-energized outputs?

If so have redundant power sources, power failure warning and
line monitoring been provided?

Have actuator fault conditions been taken into account?

Has an actuator testing schedule been created for regular actuator
maintenance ?

Have field power supplies conforming to EN61010-1 or EN 60950

been used?

Have variables been set up to report the safety accuracy value for
each channel ?

Have variables been set up to report "safe-values" when a

channels' safety accuracy value fails because it is reported to be
below the 1% accuracy figure ?

Has a maximum duration for a single channel operation of an I/O

module been specified in accordance with the application
requirements ?

Has the Shutdown option for each SIL2 or SIL3 Ouput Channel

been set to OFF.