Functional Stress

5Hz to 9Hz

Continuous

1.7mm amplitude

Occasional

3.5mm amplitude

Withstand

10Hz to 150Hz

Acceleration

0.1g in 3 axes

Endurance

10Hz to 150Hz

Acceleration

0.5g in 3 axes

Shock

15g peak, 11ms duration, ½ sine

Altitude

Operating

0 to 2000m (0 to 6,600 ft.)

Storage and Transport

0 to 3000m (0 to 10,000 ft.)
This equipment must not be transported in
unpressurized aircraft flown above 10,000 ft.

Electromagnetic Interference

Tested to the following standards: EN 61326-

1:2006, Class A; EN 61326-3-1:2008, EN 54-4:
1997, A1; EN 61131-2:2007; EN 62061:2005.

Hazardous Location Capability

Suitable for Class I Div 2 and Zone 2.

IMPORTANT

This equipment is not certified for use in a

Zone 1 location

This equipment is not certified for use in a

Zone 0 hazardous environment.

Note:
Casing: Standard AADvance modules also have a plastic casing and are rated IP20:

Protected against solid objects over 12mm (1/2in.) for example "fingers".There is no
specific protection against liquids.

Electromagnetic Immunity and Emissions

The AADvance system has been designed and tested to withstand normal

levels of conducted and radiated electromagnetic interference and electrostatic

discharge. Electrical noise conditions may vary greatly, depending on the

equipment installation, wiring, other installed equipment, and its proximity to
the AADvance equipment.
A detailed analysis of the installation electrical and magnetic conditions is rare.

It is therefore necessary to ensure that the system as a whole complies with
the client's requirements or appropriate standards EN6100-6-2:2005 and

EN6100-6-4:2007; within Europe, the CE mark requirements form a legal

minimum.