Rockwell Automation AADvance Controller Safety Manual User Manual

Page 49

background image


Document: 553630
ICSTT-RM446K-EN-P Issue: 10

_C

3-15

Table 12:

Output Modules


Modules

TÜV Certified

Configuration

Conditions

Digital Outputs

T8451, 24V dc, 8
channel.

+

T9851/2 TA,24V dc,

8 Channel,
Simplex/Dual

1oo1, 1oo2 or 1oo2D

De-energize to action (normally energized): SIL3
with 1 or 2 modules fitted. (1oo2D with dual output
modules fitted).

Energize to action (normally de-energized): SIL2
with 1 module fitted and SIL3 with 2 modules fitted.

A faulty digital output module must be repaired or
replaced within the MTTR which was used in the
PFD calculation.

Analogue Outputs

T9481/T9842
Analogue Output

Module, 3/8 Ch,
Isolated

+

T9881/T9882, TA,
8Ch, Simplex/Dual

1oo1, 1oo2 or 1oo2D De-energize to action (normally energized): SIL3

with 1 or 2 modules fitted. (1oo2D with dual output
modules fitted).

Energize to action (normally de-energized): SIL2
with 1 module fitted and SIL3 with 2 modules fitted.

A faulty analogue output module must be repaired
or replaced within the MTTR which was used in the
PFD calculation.

Table 13:

Auxiliary Modules

Modules

Conditions

Processor Base

T9100

Safety-related and can be used for safety critical applications in Fault

tolerant/High demand SIL2 applications with 2 modules fitted or
SIL3 applications with 2 or 3 modules fitted.

I/O Base

T9300 (3-way)

Safety-related and can be used for safety critical applications in SIL3.

Note: Revisions of modules are subject to change. A list of the released
versions is held by TÜV or can be obtained from Rockwell Automation.