Safety Manual (AADvance Controller)


Field Configurations

The following are recommended field loop circuits for line monitoring of

digital/analogue inputs.

Use cable monitoring and circuit integrity cable as appropriate for the

application, as inter-channel short circuits cannot be detected by an AADvance
controller.

Line Monitoring

This section provides recommended line monitoring circuits and resistor

values. You can set-up line monitoring on the following modules:

T9401 and T9402 Digital Input Modules

T9431 and T9432 Analogue Input Modules

Note: You must ensure that there is no crossover between channels.

Digital Input Field Loop Circuits

Recommended Field Loop Circuits

This section contains recommended field loop circuits for line monitoring

digital inputs used in Emergency Shutdown or Fire & Gas applications.

Field Loop Circuit for Digital Input