Field Loop Circuit for Line Monitored Digital Input for Emergency Shutdown Systems (ESD)

The suggested values for R1 and R2 are as follows:
R1 = 15K 1%, 1W (maximum power dissipated is 47mW at 26.4V)
R2 = 3K9 1%, 1W (maximum power dissipated is 182mW at 26.4V)
Suggested threshold values for both of the above circuits are as follows:
Threshold ID

Value (mV)

Maximum Allowed

=

32000

SHORT CIRCUIT

Threshold 8

=

19000

Threshold 7

=

18500

ON (nominal 16V)

Threshold 6

=

11000

Threshold 5

=

10500

INDETERMINATE

Threshold 4

=

6500

Threshold 3

=

6000

OFF (nominal 8V)

Threshold 2

=

3500

Threshold 1

=

3000

OPEN CIRCUIT

Assumptions:

Loop supply voltage = 24V ± 10%

Maximum Field Cable Line Resistance: < 100

total; this means < 50 + 50

for the two cables.