Document: 553630

ICSTT-RM446K-EN-P Issue: 10

_C

Safety Manual (AADvance Controller)


Minimum Isolation is 0.75M



between the field loop conductors.

These values will allow the input to detect more accurately different
voltage levels that represent OPEN CCT - OFF - ON - SHORT CCT and

will also detect Over Voltage and an input which is neither ON or OFF.

The values ensure that a line fault will be declared before it becomes
possible for a false declaration of On and Off states due to a combination

of resistor value drift and loop voltage variation.

Field Loop Circuit for Line Monitored Digital Input for Fire and Gas Systems (F & G)

The F&G circuit will also allow two devices to be in alarm without

reporting short circuit.

All of the input circuits are suitable for simplex, dual and TMR

configurations.

The F&G circuit assumes that the devices are volt-free contacts.

For further information, please refer to application note AN-T90001 Field

Loop Configuration. This also includes advice for fire detectors which are

not simple volt free contacts.