beautypg.com

Rockwell Automation AADvance Controller Safety Manual User Manual

Page 42

background image

3-8

Document: 553630

ICSTT-RM446K-EN-P Issue: 10

_C

Safety Manual (AADvance Controller)



If required you can configure triple processor modules as a variation of this

SIL3 architecture. Using this arrangement the processor modules operate in

2oo3D under no fault conditions and 1oo2D on the detection of the first fault
in any module. They degrade to 1oo1D on the detection of faults in any two

modules, and will fail-safe when there are faults on all three modules.

Digital Output Modules

For de-energize to action operation one digital output module is sufficient

for SIL3 requirements. However, for energize to action operation, dual

digital output modules are required.

A digital output module fault must be repaired within the MTTR which was

used in the PFD calculation.

Analogue Output Modules

The fail-safe state current of the analogue output module is less than 2mA.

For de-energize to action operation one analogue output module

is sufficient for SIL3 requirements. However, for energize to action

operation, dual analogue output modules are required.

A analogue output module fault must be repaired within the MTTR

which was used in the PFD calculation.

Table 7:

Modules for SIL3 Fail-safe I/O, Fault Tolerant Processor

Position Module Type

I/P A

T9401/2 Digital Input Module, 24V c, 8/16 Channel +

T9801 Digital Input TA, 16 Channel, Simplex or

T9431/2 Analogue Input Module, 8/16 channel + T9831
Analogue Input TA, 16 Channel, Simplex

T9300 Base unit