A system fault shall be audibly indicated. This indication may be capable of
being silenced.
The cabinet of the control and indicating equipment shall be of robust
construction, consistent with the method of installation recommended in
the documentation. It shall meet at least classification IP30 of IEC
60529:1991.
All mandatory indications shall be visible at access level 1 without prior
manual intervention such as the need to open a door.
If the control and indicating equipment is designed to be used with a
power supply (item L of figure 1 of EN 54-1) contained in a separate
cabinet, then an interface shall be provided for at least two transmission
paths to the power supply, such that a short circuit or an interruption in
one does not affect the other.
The EN54-2 certification is only applicable where the system is applied in
accordance with this safety manual and EN54-2 requirements.
EN54 section 7.12 Dependencies on More Than One Alarm Signal
7.12.1 Type A dependency (option with requirement)
Following the receipt of a first alarm signal from a fire detector, the entry to
the fire alarm condition may be inhibited until the receipt of a confirmation
alarm signal from the same fire detector, or from a fire detector in the same
zone. In this case, the first alarm state need not be indicated, and the following
shall apply:
the mode of operation shall be configurable at access level 3 for individual
zones;
reception of a confirmation alarm shall not be inhibited for more than 60s
following the receipt of the first alarm signal. The manufacturer may specify
a time shorter than 60 s. In this case, this specification shall be tested and
verified;
the first alarm state shall be automatically canceled within 30 min of the
receipt of the first alarm signal;
information on the values of the configured delay times shall be accessible
at access levels 2 or 3.