beautypg.com

Safety manual (aadvance controller) – Rockwell Automation AADvance Controller Safety Manual User Manual

Page 102

background image

4-46

Document: 553630

ICSTT-RM446K-EN-P Issue: 10

_C

Safety Manual (AADvance Controller)


For systems for applications outside Europe it is recommended that at least
the same measures be applied, and confirmation sought from the client or

end-user that electromagnetic interference (EMI) levels are within those

shown in the table.

Immunity to Electromagnetic Emmissions

Standard

Conditions

Notes

Radiated Emissions

CISPR11:2003

BS EN 61000-4:2001

+ A1:1998

+ A2:2001

Class A

N/A

Not applicable

Access to controller must be

restricted to appropriately trained
maintenance personnel operating in
accordance with and relevant ESD

mitigating procedures.

Radiated Field Immunity

BS EN 61000-4-3:2006

+A1:2008

10V rms/m (unmodulated)

80M Hz-2G Hz: 80% 1k Hz
AM

1Hz Pulse Modulation 50:50

duty cycle.

1V rms/m (unmodulated) 2G
Hz, 2.7G Hz 80%

1k Hz AM

The equipment additionally

complies with fail-safe performance
criteria at increased levels of 20V/m
over the range 80M Hz to 1G Hz

and 3V rms/m (unmodulated) over
the range 2G Hz to 2.7G Hz.

Fast Transient/Burst Immunity

BS EN 61000-4:2004

+ AC1:2006

+ AC1:2006

+ AC2:2007

DC Power:2k V

I/O and Signalling Ports:

1k V

The equipment additionally
complies with fail-safe performance

criteria at increased levels of 2KV
between I/O or signalling ports and
ground.

Surge Immunity

BS EN 61000-4-5:2006

DC Power 1k V/2k V line-

line/line-ground I/O Port: 1k
V line-ground only

The equipment additionally

complies with fail-safe performance
criteria at increased levels of 2 kV
between I/O or signalling ports and

ground.

Conducted RF Immunity

BS EN 61000-4-6:2003

+ A1:2004

+A2:2006

10V rms (unmodulated) 150k
Hz — 100M Hz 80% 1k hZ

AM, 1Hz PM 50:50 duty.

None