For systems for applications outside Europe it is recommended that at least
the same measures be applied, and confirmation sought from the client or
end-user that electromagnetic interference (EMI) levels are within those
shown in the table.
Immunity to Electromagnetic Emmissions
Standard
Conditions
Notes
Radiated Emissions
CISPR11:2003
BS EN 61000-4:2001
+ A1:1998
+ A2:2001
Class A
N/A
Not applicable
Access to controller must be
restricted to appropriately trained
maintenance personnel operating in
accordance with and relevant ESD
mitigating procedures.
Radiated Field Immunity
BS EN 61000-4-3:2006
+A1:2008
10V rms/m (unmodulated)
80M Hz-2G Hz: 80% 1k Hz
AM
1Hz Pulse Modulation 50:50
duty cycle.
1V rms/m (unmodulated) 2G
Hz, 2.7G Hz 80%
1k Hz AM
The equipment additionally
complies with fail-safe performance
criteria at increased levels of 20V/m
over the range 80M Hz to 1G Hz
and 3V rms/m (unmodulated) over
the range 2G Hz to 2.7G Hz.
Fast Transient/Burst Immunity
BS EN 61000-4:2004
+ AC1:2006
+ AC1:2006
+ AC2:2007
DC Power:2k V
I/O and Signalling Ports:
1k V
The equipment additionally
complies with fail-safe performance
criteria at increased levels of 2KV
between I/O or signalling ports and
ground.
Surge Immunity
BS EN 61000-4-5:2006
DC Power 1k V/2k V line-
line/line-ground I/O Port: 1k
V line-ground only
The equipment additionally
complies with fail-safe performance
criteria at increased levels of 2 kV
between I/O or signalling ports and
ground.
Conducted RF Immunity
BS EN 61000-4-6:2003
+ A1:2004
+A2:2006
10V rms (unmodulated) 150k
Hz — 100M Hz 80% 1k hZ
AM, 1Hz PM 50:50 duty.
None