Document: 553630
ICSTT-RM446K-EN-P Issue: 10

_C

5-7

Description

Yes/No

THe HART data is not used as the primary process measurement
in a safety related SIF ?

The HART Passthru function has been disabled if the device

configuration status is not monitored and alarmed to prevent
unauthorized or accidental changes to the field device
configuration.

Testing Checklist

Description

Yes/No

Have all of the functions and function blocks used been fully
tested?

Was CVT enabled when you compiled your application ?

Has the application been fully tested?

Are the scan and response times in accordance with the PST
requirements (< ½ PST)?

Have the climatic conditions been verified to be suitable?

Have Test Plans and Test Specifications been developed for the
system ?

Has the system been fully tested to the Test Plans and Test

Specifications ?