Diagnostics and Troubleshooting
9-1
C
HAPTER
9
Diagnostics and Troubleshooting
Observe the following precautions when troubleshooting the drive:
• Stop the drive.
• Disconnect, tag, and lockout AC power before working on the drive.
• Verify that there is no voltage present at the AC input power terminals. Refer to
figure 4.1 for the location of the terminals.
9.1
Problems Not Reported by Fault Codes
If a problem exists in the absence of a fault code, it is most likely the result of wiring or
programming. Refer to the table below to diagnose and correct some of these types
of problems.
!
ATTENTION: Only qualified personnel familiar with the construction and
operation of this equipment and the hazards involved should install,
adjust, operate, and/or service this equipment. Read and understand
this instruction manual in its entirety before proceeding. Failure to
observe this precaution could result in severe bodily injury or loss of life.
ATTENTION: After disconnecting input power, wait three minutes to
allow the DC bus capacitors to discharge. Failure to observe this
precaution could result in severe bodily injury or loss of life.
Table 9.1 – Problems Not Reported by Fault Codes
Problem
Parameter
Values to
Review
Possible Cause
Corrective Action
Drive does not
run when
commanded to
run.
d-01
d-03
d-05
P-10
- Incorrect or faulty control
wiring.
- Start control (P-10) not
set properly.
- Refer to control wiring diagrams for proper
connections. Verify condition of signals which are
intended to control drive.
- Understand and set P-10 according to control
requirements.
Drive runs,
but not at
commanded
speed.
d-00
d-01
d-02
P-05
P-20
P-21
P-40
through
P-48
- Speed reference (P-20
and/ or P-21) not set
properly.
- Speed reference not
present.
- Current limit (P-05) is set
too low.
- Load is excessive
- Understand and set P-20 and/or P-21 according to
control requirements.
- Determine which speed reference you have chosen
and then provide it.
- Increase P-05 to an operable but safe level
- Reduce load