7-22

Installing and Operating the SP200 AC Drive

d-05 Input Status

This parameter displays the status of
the inputs that are connected to the
control signal terminal block.

Parameter Range:

0000 to 7111

Running Access:

RO

Left Digit

Value

Terminal 8

(Configurable Input)

Terminal 7

(Preset 2)

Terminal 6

(Preset 1)

0

OFF

OFF

OFF

1

OFF

OFF

ON

2

OFF

ON

OFF

3

OFF

ON

ON

4

ON

OFF

OFF

5

ON

OFF

ON

6

ON

ON

OFF

7

ON

ON

ON

Digit = 1 if the Function Loss/Reset Input (#3) is ON

Digit = 1 if the Forward Run Input (#4) is ON

Digit = 1 if the Reverse Run Input (#5) is ON

Digit = 1 if the Configurable Input (#6) is ON

For Model A (Single Channel Analog), the value is formatted as follows:

Digit = 1 if the Function Loss/Reset Input (#3) is ON

Digit = 1 if the Forward Run Input (#4) is ON

Digit = 1 if the Reverse Run Input (#5) is ON

This digit represents the combination of the Preset 1, Preset 2, and Configurable Inputs as

For Model B (Preset), the value is formatted as follows:

shown in the following table:

Digit = 1 if the Configurable Input (#3) is ON

Digit = 1 if the Forward Run Input (#4) is ON

Always 0

Always 0

For Model C (Dual Channel Analog), the value is formatted as follows: