7-4

Installing and Operating the SP200 AC Drive

7.1.2 Digital Input/Output Control Parameters (Group 1)

P-10 Start Control

Model

A

B

C

Use this parameter to define the
source of the run, stop, and direction
commands.

See section 9.2 for fault reset
methods.

Parameter Range:

1 = Keypad control
2 = 2-Wire control
3 = 3-Wire control

X
X
X

X
X
X

X
X
X

Default Setting:

2

X

X

X

Running Access:

RO

P-11 Configurable Input

Model

A

B

C

Use this parameter to define how the
configurable input works.

See section 9.2 for fault reset
methods.

Parameter Range:

0 = Function Loss (P-10

3)

X

1 = Disabled

X

1 = Preset Speed

X

1 = Reverse Run (2-wire)

X

2 = Jog (P-10

1)

X

X

2 = Jog (P-10

1 or 3)

X

3 = Alternate Speed.Reference

X

X

3 = Alt. Spd. Reference (P-10

3)

X

4 = N.C. Coast to stop

X

X

4 = N.C. Coast to stop (P-10

3)

X

5 = Secondary Accel/Decel

X

X

5 = Sec. Accel/Decel (P-10

3)

X

Default Setting:

2

X

1

X

0

X

Running Access:

RO

Model A:

When P-11 is set to:

Then the configurable input works as follows:

1 (Disabled)

The configurable input not used.

2 (Jog)

When the configurable input is ON, the drive will jog at the Internal / Jog
Frequency (P-40) in the direction specified by the Reverse input.

3 (Alternate Speed Reference)

When the configurable input is ON, the drive will use the value of
parameter P-21 (Alternate Speed Reference) as the source of the
command frequency. See figure 7.1 or 7.2 for more information

4 (N.C. Coast to Stop)

When the configurable input is OFF, the drive will coast to stop.

5 (Secondary Accel/Decel)

When the configurable input is ON, the drive will use parameters P-32
(Acceleration Time 2) and P-33 (Deceleration Time 2) for the accel and
decel times.