Editing Drive Parameters

7-21

7.2

Display Parameters

Display parameters show information regarding the drive status. These parameters
are always read only.

d-00 Command Frequency

This parameter represents the
frequency that the drive is
commanded to output. This

Parameter Range:

0 to 240.0 (x.x Hz)

Running Access:

RO

command may come from any of the frequency sources selected by P-20 (Main Speed Reference) or P-21
(Alternate Speed Reference). The displayed value of this parameter can be scaled to other units by changing
P-62 (Speed Display Units).

d-01 Output Frequency

This parameter represents the output
frequency at terminals U, V, and W.
The displayed value of this parameter
can be scaled to other units by

Parameter Range:

0 to 240.0 (x.x Hz)

Running Access:

RO

changing P-62 (Speed Display Units).

d-02 Output Current

This parameter represents the output
current at terminals U, V, and W.

Parameter Range:

0 to 200% of rated current (x.x amps RMS)

Running Access:

RO

d-03 Bus Voltage

This parameter represents the DC
bus voltage level.

Parameter Range:

0 to 500 for 230 V drives;
0 to 1000 for 460 V drives.

Running Access:

RO

d-04 Fault Code

This parameter represents the fault
code for the last detected fault. Refer
to chapter 9 for troubleshooting code

Parameter Range:

alphanumeric code

Running Access:

RO

definitions.