Rockwell Automation SP200 AC Drive, 1 2 Channel Analog, Preset Speed User Manual
Page 25
Editing Drive Parameters
7-3
P-03 Reverse Disable
Model
A
B
C
This parameter enables or disables
output frequency in the reverse
direction. If reverse is disabled, a
reverse command will be ignored.
Parameter Range:
0 = Reverse enabled
1 = Reverse disabled
X
X
X
X
X
X
Default Setting:
0
X
X
X
Running Access:
RO
P-04 Auto Restart Attempts
Model
A
B
C
Use this parameter to select the
number of times the drive will attempt
to restart after the occurrence of an
auto-resettable fault (listed in table
9.2).
Parameter Range:
0 to 10
X
X
X
Default Setting:
0
X
X
X
Running Access:
RW
If the value for this parameter is nonzero, the drive will wait for 1 second after an auto-resettable fault occurs
and then clear the fault and attempt to restart the drive automatically.
Once the drive restarts, it must run for 5 minutes without faulting to restore the number of attempts specified by
this parameter.
The auto restart sequence is terminated if the drive is intentionally stopped.
!
ATTENTION : If parameter P-04
≠
0, the drive will attempt to restart automatically after the occurrence of
an auto-resettable fault. When this feature is enabled, the user must ensure that automatic restart of the driven
equipment will not cause injury to operating personnel or damage to the driven equipment.
P-05 Current Limit
Model
A
B
C
Use this parameter to specify the
drive current limit. When the drive is
operating at commanded speed, and
the current subsequently reaches this
value, the drive output frequency and
Parameter Range:
10 to 150 (%)
X
X
X
Default Setting:
150
X
X
X
Running Access:
RW
voltage are reduced until the current limit is not exceeded. At this point, it will accelerate back to the reference
speed. If the current limit is exceeded while accelerating, the acceleration time will be automatically increased
until the current limit is not exceeded.