P.003 minimum speed, P.004 maximum speed – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual
Page 95
Programming Reference
4-9
Note that in V/Hz regulation, the drive may decrease the output frequency below P.003
(but not below 0.5 Hz) to avoid an overcurrent fault.
For V/Hz regulation, this parameter specifies the maximum allowed speed in hertz.
The drive is equipped with configurable overspeed protection at the frequency level
set in H.022 (Overfrequency Limit).
For vector regulation, this parameter specifies the maximum allowed speed in RPM.
The drive is equipped with fixed overspeed protection at 130% of Maximum Speed.
P.003 Minimum Speed
This parameter limits
the speed reference
to the drive.
Regardless of what
speed reference is
supplied, the
regulator will not
command a speed
less than the value in
P.003.
Parameter Range:
0.5 to P.004 Maximum Speed (V/Hz)
0 to P.004 Maximum Speed (vector)
Default Setting:
5.0 Hz (V/Hz)
150 RPM (vector)
Parameter Type:
Tunable
Refer also to parameters:
P.004 Maximum Speed
!
ATTENTION: The drive can operate at and maintain zero speed. The
user is responsible for ensuring safe conditions for operating personnel
by providing suitable guards, audible or visual alarms, or other devices
to indicate that the drive is operating or may operate at or near zero
speed. Failure to observe this precaution could result in severe bodily
injury or loss of life.
P.004 Maximum Speed
This parameter limits
the speed reference
to the drive.
Regardless of what
speed reference is
supplied, the
regulator will not
command a speed
greater than the
value in P.004.
Parameter Range:
15.0 to H.022 Overfrequency Limit (V/Hz)
10 RPM to U.017 Motor Top Speed (vector)
Default Setting:
60.0 Hz (V/Hz)
1722 RPM (vector)
Parameter Type:
Tunable
Refer also to parameters:
P.028 Speed Display Scaling
H.022 Overfrequency Limit
U.017 Motor Top Speed
!
ATTENTION: The user is responsible for ensuring that driven machinery,
all drive-train mechanisms, and application material are capable of safe
operation at the maximum operating speed of the drive. Overspeed
detection in the drive determines when the drive shuts down. For vector
regulation, this is factory-set to 130% of maximum speed. For volts/hertz
regulation, this is fixed at the frequency level set in parameter H.022
(Overfrequency Limit). Failure to observe this precaution could result in
bodily injury.