Programming Reference

4-9

Note that in V/Hz regulation, the drive may decrease the output frequency below P.003

(but not below 0.5 Hz) to avoid an overcurrent fault.

For V/Hz regulation, this parameter specifies the maximum allowed speed in hertz.

The drive is equipped with configurable overspeed protection at the frequency level

set in H.022 (Overfrequency Limit).

For vector regulation, this parameter specifies the maximum allowed speed in RPM.

The drive is equipped with fixed overspeed protection at 130% of Maximum Speed.

P.003 Minimum Speed

This parameter limits

the speed reference

to the drive.

Regardless of what

speed reference is

supplied, the

regulator will not

command a speed

less than the value in

P.003.

Parameter Range:

0.5 to P.004 Maximum Speed (V/Hz)

0 to P.004 Maximum Speed (vector)

Default Setting:

5.0 Hz (V/Hz)

150 RPM (vector)

Parameter Type:

Tunable

Refer also to parameters:

P.004 Maximum Speed

!

ATTENTION: The drive can operate at and maintain zero speed. The

user is responsible for ensuring safe conditions for operating personnel

by providing suitable guards, audible or visual alarms, or other devices

to indicate that the drive is operating or may operate at or near zero

speed. Failure to observe this precaution could result in severe bodily

injury or loss of life.

P.004 Maximum Speed

This parameter limits

the speed reference

to the drive.

Regardless of what

speed reference is

supplied, the

regulator will not

command a speed

greater than the

value in P.004.

Parameter Range:

15.0 to H.022 Overfrequency Limit (V/Hz)

10 RPM to U.017 Motor Top Speed (vector)

Default Setting:

60.0 Hz (V/Hz)

1722 RPM (vector)

Parameter Type:

Tunable

Refer also to parameters:

P.028 Speed Display Scaling

H.022 Overfrequency Limit

U.017 Motor Top Speed

!

ATTENTION: The user is responsible for ensuring that driven machinery,

all drive-train mechanisms, and application material are capable of safe

operation at the maximum operating speed of the drive. Overspeed

detection in the drive determines when the drive shuts down. For vector

regulation, this is factory-set to 130% of maximum speed. For volts/hertz

regulation, this is fixed at the frequency level set in parameter H.022

(Overfrequency Limit). Failure to observe this precaution could result in

bodily injury.