3.6 Drive Status LEDs

The keypad contains eight LEDs that show the present drive status. Table 3.2

describes what each drive status LED means.

Table 3.2 – Drive Status LEDs

LED

Status

Meaning

RUNNING

On

Output power is being applied to the motor.

Off

Output power is not being applied to the motor.

REMOTE

On

The drive is being controlled (START, RUN/JOG,

FORWARD/REVERSE, speed reference) from a source

other than the keypad.

Off

The drive is being controlled from the keypad.

Flashing The network connection is lost.

JOG

On

Jog is selected.

Off

Run is selected.

AUTO

On

The drive is receiving its speed reference from the

terminal strip input or network option.

Off

The drive is receiving its speed reference from the local

keypad or serial port (OIM or CS3000), i.e., using a

manual reference.

FORWARD

1

1

If the speed reference is zero (0), pressing the FORWARD/REVERSE key (or toggling the FWD/REV

input) will not alter the state of the FORWARD or REVERSE LEDs.

Flashing The requested motor direction is forward; the actual

motor direction is reverse (REVERSE LED is on).

On

The motor is running in the forward direction.

Off

The motor direction is not forward.

REVERSE

1

Flashing The requested motor direction is reverse; the actual

motor direction is forward (FORWARD LED is on).

On

The motor is running in the reverse direction.

Off

The motor direction is not reverse.

PROGRAM

On

The keypad/display is in program mode.

Off

The keypad/display is in monitor mode.

PASSWORD On

Parameters cannot be modified from the keypad without

entering the correct password into P.051 (Programming

Disable). See section 4.4, Ensuring Program Security,

for more information.
Note that disabling program changes by means of P.051

does not prevent parameter changes being made from

the serial port or the network.

Off

Parameters can be modified from the keypad.