Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual
Page 198
![background image](/manuals/581328/198/background.png)
C-2
GV3000/SE AC Drive Software Reference, Version 6.06
Second Menu General Parameters (USA Defaults)
Second Menu Volts/Hertz Parameters (USA Defaults)
Second Menu Vector Parameters (USA Defaults)
Parameter
No.
Parameter
Name
Power Module
25G4160
25G4260
25V4160
25V4260
30V4160
30V4260
40V4160
40V4260
50V4160
50V4260
50R4160
50T4160
60G4160
60G4260
75R4160
75T4160
P.047
Carrier Freq.
(kHz)
8
8
8
8
8
2
8
2
Parameter
No.
Parameter
Name
Power Module
25G4160
25G4260
25V4160
25V4260
30V4160
30V4260
40V4160
40V4260
50V4160
50V4260
50R4160
50T4160
60G4160
60G4260
75R4160
75T4160
H.002
Motor Namepl.
Amps
29.7
29.7
35.5
48.7
62.5
68.0
68.0
85.1
Parameter
No.
Parameter
Name
Power Module
25G4160
25G4260
25V4160
25V4260
30V4160
30V4260
40V4160
40V4260
50V4160
50V4260
50R4160
50T4160
60G4160
60G4260
75R4160
75T4160
U.004
Motor Namepl.
Amps
27.0
30.0
35.5
48.7
62.5
65.0
65.0
77.0
U.005
Motor Namepl.
RPM
1770
1770
1770
1775
1775
1780
1780
1780
U.006
Magnetizing
Current
52.0
44.0
44.0
47.0
44.0
49.0
49.0
46.0
U.012
Speed Reg.
Prop. Gain
5.00
5.00
5.00
5.00
5.00
10.00
5.00
10.00
U.013
Speed Reg. Int.
Gain
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
U.014
Torque Reg.
Prop. Gain
0.40
0.40
0.40
0.40
0.40
0.20
0.40
0.20
U.015
Torque Reg.
Integral Gain
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
U.016
Field Weaken
Start RPM
1770
1770
1770
1775
1775
1780
1780
1780
U.017
Motor Top
Speed
1770
1770
1770
1775
1775
1780
1780
1780
U.019
Flux Current
Reg. Prop. Gain
0.30
0.30
0.30
0.30
0.30
0.15
0.30
0.15
U.20
Flux Current
Reg. Int. Gain
50.0
50.0
50.0
50.0
50.0
50.0
50.0
50.0
U.21
Rotor Time
Constant
250
250
250
250
250
350
250
350
U.022
Motor Namepl.
HP
20.0
25.0
30.0
40.0
50.0
60.0
50.0
75.0
U.032
SVC Flux Curr.
Reg. Gain
900
850
800
750
700
650
700
600