U.000 torque reference source – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual
Page 154
4-68
GV3000/SE AC Drive Software Reference, Version 6.06
4.6.4 Second Menu Vector Parameter Descriptions (U.000 to U.048)
If U.000 = 0, the drive will always regulate speed.
If U.000 > 0, the drive will regulate torque or speed. Torque or speed regulation is
selected by a terminal strip digital input (see the P.007 configuration) or the network
option board (depending on the control source).
If torque regulation is selected:
•
the Current Limit parameter (P.005) is not applied.
•
asserting the START input when JOG is selected will enable the torque regulator,
not the speed regulator (i.e., P.020, P.021, and P.022 are not used).
•
the stop type will always be coast-to-rest regardless of the value in P.025 (Stop
Type).
If U.000 = 1, the analog input conditioning (P.009 through P.011) does not apply. The
analog input in this case is converted every torque regulator scan (0.5 ms) for external
closed-loop control (e.g., positioning applications using the QUIQ module).
If U.000 = 3:
•
The FWD/REV input can be used to invert the selected speed reference when it is
used as the torque reference.
•
If the speed reference is used as the torque reference, the %torque is computed as
Speed value x 150 = %torque reference
U.017 (Top Speed)
This assumes that P.028 = U.017.
U.000 Torque Reference Source
This parameter
specifies the source
for the torque
reference when
torque regulation is
selected.
Parameter Range:
0 = Speed loop output
1 = Terminal strip analog input
2 = Option port (network torque reference register)
*
3 = Selected speed reference
*
If the AutoMax Network option is used, see P.063.
Default Setting:
0
Parameter Type:
Configurable
Refer also to parameters:
P.007 Terminal Strip Digital Inputs Configure