beautypg.com

P.024 mop reset configuration, P.025 stop type – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 115

background image

Programming Reference

4-29

Important: If the drive is powered down and powered back up, the MOP function

reference will always be reset to equal Minimum Speed (P.003).

The MOP provides a digital speed reference that can be increased and decreased

using terminal strip digital inputs.

When the MOP function is set and then disabled by using parameter P.008 (Terminal

Strip Speed Reference Source), the last value in effect prior to the MOP being

disabled will be retained.

A function loss or a fault will always cause a coast-to-rest stop.

If the drive is configured as a torque regulator (U.000 > 0 and TRQ/SPD digital input =

TRQ), then the stop type will always be coast-to-rest regardless of the value in

parameter P.025.

P.024 MOP Reset Configuration

This parameter

determines when and

if the MOP (Motor

Operated

Potentiometer)

reference is reset to

Minimum Speed

(P.003).

Parameter Range:

0 = Reset MOP reference after IET

1 = Reset MOP reference during each stop

2 = Do not reset MOP reference

Default Setting:

0

Parameter Type:

Tunable

Refer also to parameters:

P.003 Minimum Speed

P.008 Terminal Strip Speed Reference Source

P.025 Stop Type

This parameter

selects how the

motor will stop when

a stop command is

given.

Parameter Range:

0 = Coast-to-rest stop
1 = Ramp stop

Default Setting:

0

Parameter Type:

Tunable

Refer also to parameters:

P.002 Decel Time 1

P.018 Decel Time 2

P.022 Jog Ramp Decel Time

U.000 Torque Reference Source

!

ATTENTION: The user must provide an external, hardwired emergency

stop circuit outside the drive circuitry. This circuit must disable the system

in case of improper operation. Uncontrolled machine operation may

result if this procedure is not followed. Failure to observe this precaution

could result in bodily injury.