U.042 outer control loop lead/lag low frequency, U.043 outer control loop lead/lag ratio – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual
Page 173
Programming Reference
4-87
This parameter sets the lead break frequency if U.041(Outer Control Loop Lead/Lag
Select) = 1 (lead/lag) or the lag break frequency if U.041 = 2 (lag/lead). The upper limit
may be restricted by the lead/lag ratio setting (U.043).
See Appendix H for the outer control loop block diagram.
The high break frequency is determined by the values in parameters U.042 (Outer
Control Loop Lead/Lag Low Frequency) and U.043 as shown:
High break frequency = Low frequency x ratio = U.042 x U.043
See Appendix H for the outer control loop block diagram.
U.042 Outer Control Loop Lead/Lag Low Frequency
This parameter
specifies the lead/lag
low break frequency
of the outer control
loop feedback.
Parameter Range:
0.01 to 34.90 radians/second
Default Setting:
1.0
Parameter Type:
Tunable
Refer also to parameters:
U.040 Outer Control Loop Feedback Source
U.041 Outer Control Loop Lead/Lag Select
U.043 Outer Control Loop Lead/Lag Ratio
U.044 Outer Control Loop Reference Gain
U.045 Outer Control Loop Proportional Gain
U.046 Outer Control Loop Integral Gain
U.047 Outer Control Loop Trim Range Percentage
U.048 Outer Control Loop Proportional Trim Enable
U.043 Outer Control Loop Lead/Lag Ratio
This parameter
specifies the ratio
between the lead/lag
low break frequency
and high break
frequency of the
outer control loop
feedback lead/lag
block.
Parameter Range:
2 to 20
Default Setting:
10
Parameter Type:
Tunable
Refer also to parameters:
U.040 Outer Control Loop Feedback Source
U.041 Outer Control Loop Lead/Lag Select
U.042 Outer Control Loop Lead/Lag Low Frequency
U.044 Outer Control Loop Reference Gain
U.045 Outer Control Loop Proportional Gain
U.046 Outer Control Loop Integral Gain
U.047 Outer Control Loop Trim Range Percentage
U.048 Outer Control Loop Proportional Trim Enable