The time the motor takes to make any speed decrease (except a coast-to-rest stop) is

directly proportional to the value in this parameter. This parameter does not apply if

JOG is selected. See P.022 (Jog Ramp Decel Time).

Note that motor load inertia and input line conditions can extend the deceleration time

to a value greater than the preset time. With very fast deceleration times, regenerative

motor voltage may charge up the DC bus voltage, causing a high bus voltage (HU)

fault. To avoid a fault condition, extend the deceleration time for a longer period. If a

deceleration time faster than the acceptable range is required, installing an optional

Snubber Resistor Kit or Regenerative Braking Module Kit may prevent the fault.

For V/Hz regulation with dynamic braking (snubber resistor) disabled (H.017 = 0, 2, or

4), the deceleration time may be extended to prevent a high bus voltage (HU) fault

from occurring.

P.002 Decel Time 1 (RAMP 1)

For V/Hz regulation,

this parameter

specifies the amount

of time in which the

motor ramps from

Maximum Speed

(P.004) to zero

speed.

For vector regulation,

this parameter

specifies the amount

of time in which the

motor ramps from

Motor Top Speed

(U.017) to zero

speed.

Parameter Range:

1.0 to 999.9 seconds (V/Hz)

0.1 to 999.9 seconds (vector)

Default Setting:

20.0

Parameter Type:

Tunable

Refer also to parameters:

P.004 Maximum Speed

P.005 Current Limit

U.017 Motor Top Speed

U.024 High DC Bus Fault Avoidance Enable