H.018 Volts/Hertz Curve Type
(continued)
Figure 4.13 – Volts/Hertz Curve Selection
H.019 Identification Result
This parameter
displays the result of
the identification
procedure. Normally,
the identification
procedure will be
successful, and the
value in H.019 will
be = 0.
Parameter Range:
0 = Identification procedure successful. No fault.
1 = A logged error aborted the identification
procedure. Refer to section 5.3 for how to
determine the cause of the fault. Remove the
cause and repeat the procedure.
2 = A function loss aborted the identification
procedure. Depending on Function Loss
Response (P.026), this is or is not logged.
Remove the cause and repeat the procedure.
3 = A stop command aborted the identification
procedure. Repeat the procedure without
stopping.
4 = The identification procedure aborted because
the measured current feedback signal is too low.
Feedback signal elements or wiring is defective.
Check motor connections, inverter wiring, and
feedback devices (current sensors). Repeat
procedure.
6 = Calculation result based on identification
procedure measurements is out of range. Check
causes of incorrect measurements, such as
motor connections. Repeat procedure.
Default Setting:
0
Parameter Type:
Read only
Refer also to parameters:
H.020 Identification Request
Motor
Voltage
(H.000)
Volts
Hz
Motor
Base Frequency
(H.001)
Motor
Voltage
(H.000)
Volts
Hz
Motor
Base Frequency
(H.001)
Motor
Voltage
(H.000)
Volts
Hz
Motor
Base Frequency
(H.001)
Linear (0)
Optimized (1)
Squared (2)