3Ć9

3.2.2

Output Parameters for the TOF Instruction

This table lists the outputs for the TOF instruction and the variable type and data

type/range that each output supports.

Parameter

Description

Variable Type

Data Type/Range

ENO

Use this output as the input to another instruction for

easily chaining multiple instructions. ENO follows the state

of EN.

Connect a contact coil or Boolean input to

Q

This output is false when the value in Elapsed equals the

value in TPreset.
This output is true while EN is true and Elapsed is less

than TPreset.

Connect a contact, coil, or Boolean input to

another instruction.

T

This output is true while EN is false and the value in

Elapsed is less than the value in TPreset.
T is false while EN is true or the value in Elapsed equals

the value in TPreset.

Elapsed

This value is specified in increments of 0.01 seconds. This

value is incremented when EN is false, until its value

equals that of TPreset. The value in Elapsed is reset to

zero when EN is true.
The value in Elapsed is stored in the element

name.Elapsed and will not exceed the preset value when

the instruction is enabled.

constant

double integer

(0 to 2147483647)

0 to 248.5 days in

0.01 second intervals