3Ć5

3.1.2

Output Parameters for the RTO Instruction

This table lists the outputs for the RTO instruction and the variable type and data

type/range that each output supports.

Parameter

Description

Variable Type

Data Type/Range

ENO

Use this bit as the input to another instruction for easily

chaining multiple instructions. This output follows the

state of EN.

Connect a contact, coil, or Boolean input to

another instruction.

Q

This output is true when the value in Elapsed equals the

value in TPreset.
Q is false when R is true.

Connect a Boolean input or a coil.

T

This output is true when all of the following conditions are

met:
D the instruction is enabled
D the value in Elapsed is less than the value in TPreset
D TR is false
T is false when the instruction is disabled or the value in

Elapsed equals the value in TPreset.

Connect a Boolean input or a coil.

Elapsed

This value is specified in increments of 0.01 seconds. This

value is incremented when EN is true and until its value

equals that of TPreset. The value in Elapsed is reset only

when TR is true.
The value in Elapsed is stored in the element

name.Elapsed and will not exceed the TPreset value when

the instruction is enabled.

constant

double integer

(0 to 2147483647)

0 to 248.5 days in

0.01s intervals