7Ć12

7.3.3

Errors Caused by the Convert From Binary Data to Integer Data Instruction

These errors can occur when you are using the BCD_TO instruction in a program. They

are logged in the error log.

If this error occurs:

Then:

Do the following:

The result is larger

than what Out's data

type supports.

ENO is set according

to ERROR_ENO, and

Out contains the

largest value allowed

for the data type being

used.

Specify a larger data

type for Out. For

example, use a double

integer data type

instead of a integer.

An illegal BCD digit

was found.

D Out contains the

value of 0

D ENO is set

according to

ERROR_ENO.

Use a valid BCD value

for In.