10Ć39

10.7.2

Errors Caused by the MultiĆArray Instruction

Errors can occur when parameters are latched and checked. If an error occurs at this

point, no operation occurs.
If an arithmetic error occurs during the instruction's operation, a default value is

generated and the operation continues.
When an error occurs:
D ENO is set to ERROR_ENO.
D When AR2 is complete,

D the ER output is set true and retains its value until EN goes false
D the Index output points to the first entry that caused the error

These errors can occur when you are using the AR2 instruction in a program:

If this error occurs:

Do the following:

The result of the arithmetic calculation

is too large for Out.

Use smaller values or reĆarrange the

calculation so that errors do not ocĆ

cur.

Cannot divide by zero.
(As a result, Out contains the largest

signed value allowed for Out's data

type.)

Make sure that the In2 contains valĆ

ues greater than 0.

Array's length inputs are greater than

1 but are not equal.

Make sure the values are equal.

The Elems/Scan input is less than 0.

Specify a value of 0 or greater.