8Ć11

8.3.1

Input Parameters for the Masked Move Instruction

This table lists the inputs for the MVM instruction and the variable type and data

type/range that each input supports.

Parameter

Description

Variable Type

Data/Type Range

EN

While this input is true, the instruction executes. When this

input is false, the instruction is not executed and ENO is

false.

Connect a Boolean input or output.

In

Enter a constant or variable that you want to copy to Out.

In is the source of the masked move operation.

D simple
D constant
D element of an array

D integer
D double integer
D timer

(name.TPreset and

name.Elapsed)

D counter

(name.CPreset

and name.Current)

Mask

Enter a variable or hexadecimal constant that specifies

which bits to pass or block. A bit set as 1 in the mask

passes the source bit into the destination. Whereas, a bit

set as 0 blocks the source bit from being copied to the

destination. See Defining a Mask" (section 8.0).
Note: Any constants entered are displayed in hexadecimal.

D simple
D element of an array
D hexadecimal

constant

D integer
D double integer
D timer

(name.TPreset and

name.Elapsed)

D counter

(name.CPreset

and name.Current)