Chapter 3 Power Connections
AC Power Connections
PanelView Plus devices with an integrated AC power supply have
these power ratings.
The input power terminal block supports these wire sizes.
Wire Specifications for AC Power Terminal Block
Protective Earth Connection
PanelView Plus devices with an AC power input have a protective
earth/ground terminal that you must connect to a low-impedance
earth/ground.
The protective earth/ground connection is on the power input
terminal block. The protective earth terminal requires a minimum wire
gauge.
Protective Earth Wire Specifications for AC Power
Terminal
Voltage Range
Frequency
V A
400 and 600
85…264V AC
47…63 Hz
60V A max
700 to 1500
85…264V AC
47…63 Hz
160V A max
Terminal
Wire Type
Dual-wire Gauge
(1)
Single-wire Gauge
Terminal Screw Torque
400 and 600
Stranded
or solid
Cu 90 °C (194 °F)
22…16 AWG
22…14 AWG
0.45…0.56 Nm (4…5 lb•in)
700 to 1500
22…16 AWG
22…14 AWG
0.56 Nm (5 lb•in)
(1)
Two-wire max. per terminal
ATTENTION
The protective earth connection is required for both electrical
safety and Electromagnetic Compliance (EMC) with the
European Union (EU) EMC directive for CE-mark conformance.
Terminal
PE Symbol
Wire Type
Wire Gauge
Terminal Screw Torque
400 and 600
Stranded
or solid
Cu 90 °C (194
°F)
14…12 AWG
0.45…0.56 Nm (4…5 lb•in)
700 to 1500
14…12 AWG
0.56 Nm (5 lb•in)