Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual
Page 167
Publication 2711P-UM001J-EN-P - November 2009
167
Terminal Connections Chapter 7
P
anelView Plus and PanelView Plus CE Terminals to PLC-5 and MicroLogix Controllers
Cables: PanelView Plus and PanelView Plus CE to PLC-5 and
MicroLogix Controllers
Protocol
PanelView Plus Comm Port
PLC-5, PLC-5C, PLC-5E
CH0 (25-pin RS-232)
(DF1)
MicroLogix 1400, 1500LRP
CH1/CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000, 1100, 1200,
1400, 1500LSP
CH0 (8-pin Mini DIN)
(DF1 or DH-485)
MicroLogix 1100, 1400
Ethernet
DF1
(any)
RS-232 (DF1) Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft)
(null modem not required)
(4)
(4)
The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply.
N/A
DH-485
(any)
RS-232 (DH-485) Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C
N/A
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft)
(null modem not required)
(4)
N/A
DH-485 Port
PanelView Plus 400 and 600
2711P-RN3
(2)
PanelView Plus 700 to 1500
2711P-RN6, -RN6K
(2)
For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).
N/A
N/A
Use AIC+ Module
(1761-NET-AIC)
Connect to Port 3
N/A
ControlNet
ControlNet Port
PanelView Plus 400 and 600
2711P-RN15C
PanelView Plus 400 to 1500
2711P-RN15S, -RN15SK
To PLC-5C with
ControlNet Cable
N/A
N/A
N/A
DeviceNet
(1)
(1)
DeviceNet and Remote I/O communication modules are no longer available. Cable information is provided for reference only.
DeviceNet Port
PanelView Plus 400 and 600
2711P-RN10C
PanelView Plus 700 to 1500
2711P-RN10H
Use 1771-SDN Module
with DeviceNet Cable
N/A
N/A
N/A
EtherNet/IP
EtherNet/IP Port
PanelView Plus 400 to 1500
All except 2711P-xxx5xx
To PLC-5E with
1585J-M Type Cable or
2711P- CBL-EX04 (4 m/14 ft)
(3)
(3)
For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable.
Use 1761-NET-ENI Module
with Ethernet Cable
1585J-M Type Cable or
2711P- CBL-EX04 (4 m/14 ft)
Remote I/O
Remote I/O Port
PanelView Plus 400 to 1500
2711P-RN1, 2711P-RN6
Shielded Twinaxial Cable
(1770-CD)
N/A
N/A
N/A
DH+
DH+ Port
PanelView Plus 400 and 600
2711P-RN8
PanelView Plus 700 to 1500
2711P-RN6, -RN6K
Shielded Twinaxial Cable
(1770-CD)
N/A
N/A
N/A