Minimum requirements – Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual
Page 183
Publication 2711P-UM001J-EN-P - November 2009
183
Terminal Connections Chapter 7
Minimum Requirements
The software and firmware must be installed on the development
computer and the PanelView Plus terminal to configure and
communicate with an Allen-Bradley controller on a ControlNet
network.
ControlNet Unscheduled Communication
ControlNet Scheduled Communications
Software/Firmware
PanelView Plus 700 to 1500
PanelView Plus 400 or 600
FactoryTalk View Studio
Version 3.10 or later
Version 4.0 or later
FactoryTalk View Machine Edition Runtime
Version 3.10 or later
Version 4.0 or later
ControlNet Module Firmware
2711P-RN15S, Series A, Rev A
(firmware version 2.07 or later)
(1)
2711P-RN15C, Series B, Rev A
or later
(1)
This applies to terminals that are ordered as pre-configured units with the ControlNet module.
Requirements
PanelView Plus 700 to 1500
PanelView Plus 400 or 600
FactoryTalk View Studio
Version 3.20 or later
Version 4.0 or later
FactoryTalk View Machine Edition Runtime Version 3.20.04 or later
Version 4.0 or later
RSNetWorx for ControlNet
Version 5.11 or later
Version 6.0 or later
RSLogix 5000
Version 13.0 or later
Version 15.0 or later
ControlNet Module Firmware
2711P-RN15S, Series A, Rev C
(firmware version 3.08 or later)
(1)
2711P-RN15C, Series B, Rev A
or later
(1)
This applies to terminals that are ordered as preconfigured units with the ControlNet module.
WARNING
The ControlNet Communications Module, cat. no.
2711P-RN15S, will not run with FactoryTalk View ME firmware
version 3.20.04 or earlier. All ControlNet Modules with version
3.07 firmware must be upgraded to version 3.08 or later;
otherwise, outputs may turn on an indeterminate state.