Startup Information
Messages
Startup messages display in a specific sequence on the terminal during
startup and typically display for a few seconds. These messages
indicate the startup sequence of the terminal, but do not require that
you perform any action.
Message #
Displayed Message
Description
37
(1)
Video Initialized
Configures and initializes the graphics video system.
30
Watchdog Test
Tests the watchdog circuitry to verify system integrity.
1
RAM Test
Tests the RAM memory.
Stuck Key
Checks the integrity of the function key hardware.
31.5
Stuck Touch
Checks the integrity of the touch screen hardware.
Battery Test
Checks the integrity of the battery hardware.
2.5
Registry Search
Locates and loads the most recent, valid registry. Multiple copies of the registry are
maintained. If power is lost during a registry update, a valid registry is available the next
time power is applied to the terminal.
2
Image Search
Checks for new OS firmware upgrade on the external CompactFlash card and the serial port.
11
(2)
Downloading Image
Downloads a new OS firmware upgrade to internal RAM. Message may remain on screen
for several minutes.
External CF
Transfers a new OS firmware upgrade from the external CompactFlash card to the terminal.
Message may display for several minutes.
20
(2)
Transfer Image
Programs the OS firmware just downloaded into RAM. Message may remain on screen for
several minutes.
Internal CF
Programs the OS firmware just downloaded into the internal flash memory. Message may
display for several minutes.
24
CRC Check
Checks the integrity of the OS firmware.
27
(2)
Decompress System
Decompresses the compressed OS firmware into RAM.
28
Starting System
Launches the operating system (OS).
29
System Check ###
Checks internal file system integrity (### is percent progress indicator).
29.1
System Check
Disables internal file system integrity check. Contact technical support.
(1)
The status number and message displays only on the 700 to 1500 terminals.
(2)
The status number and message displays only on the 400 and 600 terminals.