beautypg.com

Ethernet/ip to cip serial, Use modems with micro800 controllers, Making a df1 point-to-point connection – Rockwell Automation 2080-LC20-20QBBR Micro820 20-point Programmable Controllers User Manual User Manual

Page 49: Construct your own modem cable

background image

Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

41

Communication Connections Chapter 5

EtherNet/IP to CIP Serial

Use Modems with
Micro800 Controllers

Serial modems can be used with the Micro820 controllers.

Making a DF1 Point-to-Point Connection

You can connect the Micro820 programmable controller to your serial modem.
The recommended protocol for this is Modbus RTU.

Construct Your Own Modem Cable

If you construct your own modem cable, the maximum cable length is 3 m (10 ft)
with a 25-pin or 9-pin connector. Refer to the following typical pinout for
constructing a straight-through cable:

EtherNet/IP

CIP Serial

Micro820
Controller

Micro820
Controller

46046

IMPORTANT

Micro800 controllers do not support more than one hop (for example,
from EtherNet/IP → CIP Serial → EtherNet/IP).

DTE Device
(Micro820
Channel 0)

DCE Device
(Modem, etc.)

n

i

P

-

9

n

i

P

-

5

2

n

i

P

-

6

3

2

D

X

T

D

X

T

5

2

3

D

X

R

D

X

R

4

5

7

D

N

G

D

N

G

6

1

8

D

C

D

)

+

(

B

1

4

0

2

R

T

D

)-

(

A

2

6

6

R

S

D

3

8

5

S

T

C

7

4

S

T

R

D

N

G