beautypg.com

Embedded ethernet support – Rockwell Automation 2080-LC20-20QBBR Micro820 20-point Programmable Controllers User Manual User Manual

Page 12

background image

4

Rockwell Automation Publication 2080-UM005A-EN-E - December 2013

Chapter 1

Hardware Overview

The communication port (both RS232 and RS485) are non-isolated. The signal
ground of the port is not isolated to the logic ground of the controller.

The RS232 port supports connection to the Micro800 Remote LCD module
(2080-REMLCD).

Embedded Ethernet Support

A 10/100 Base-T Port is available for connection to an Ethernet network through
any standard RJ-45 Ethernet cable.

RS232/RS485 Serial Port Pin Definition

Pin

Definition

RS485
Example

RS232
Example

1

RS485+

RS485+

(not used)

2

RS485-

RS485-

(not used)

3

GND

GND

GND

4

RS232 input (receiver)

(not used)

RxD

5

RS232 output (driver)

(not used)

TxD

6

GND

GND

GND

REMLCD to Micro820 Serial Port Terminal Block Wiring

REMLCD Serial Port
Terminal Block

Micro820 Serial Port
Terminal Block

Signal

Pin
number

Pin
number

Signal

RS232 TX

1

<-------->

4

RX RS232

RS232 RX

2

<-------->

5

TX RS232

RS232 G

3

<-------->

6

G RS232

D-

D+

G

Rx

Tx

1

2

3

4

5

6

G

RJ-45 connector

RJ-45 Ethernet Port Pin Mapping

Contact
Number

Signal

Direction Primary

Function

1

TX+

OUT

Transmit data +

2

TX-

OUT

Transmit data -

3

RX+

IN

Receive data +

4

5

6

RX-

IN

Receive data -

7

8

46210

1

8