4
Rockwell Automation Publication 2080-UM005A-EN-E - December 2013
Chapter 1
Hardware Overview
The communication port (both RS232 and RS485) are non-isolated. The signal
ground of the port is not isolated to the logic ground of the controller.
The RS232 port supports connection to the Micro800 Remote LCD module
(2080-REMLCD).
Embedded Ethernet Support
A 10/100 Base-T Port is available for connection to an Ethernet network through
any standard RJ-45 Ethernet cable.
RS232/RS485 Serial Port Pin Definition
Pin
Definition
RS485
Example
RS232
Example
1
RS485+
RS485+
(not used)
2
RS485-
RS485-
(not used)
3
GND
GND
GND
4
RS232 input (receiver)
(not used)
RxD
5
RS232 output (driver)
(not used)
TxD
6
GND
GND
GND
REMLCD to Micro820 Serial Port Terminal Block Wiring
REMLCD Serial Port
Terminal Block
Micro820 Serial Port
Terminal Block
Signal
Pin
number
Pin
number
Signal
RS232 TX
1
<-------->
4
RX RS232
RS232 RX
2
<-------->
5
TX RS232
RS232 G
3
<-------->
6
G RS232
D-
D+
G
Rx
Tx
1
2
3
4
5
6
G
RJ-45 connector
RJ-45 Ethernet Port Pin Mapping
Contact
Number
Signal
Direction Primary
Function
1
TX+
OUT
Transmit data +
2
TX-
OUT
Transmit data -
3
RX+
IN
Receive data +
4
–
–
–
5
–
–
–
6
RX-
IN
Receive data -
7
–
–
–
8
–
–
–
46210
1
8
- 2080-LC20-20AWBR Micro820 20-point Programmable Controllers User Manual 2080-LC20-20QWBR Micro820 20-point Programmable Controllers User Manual 2080-LC20-20AWB Micro820 20-point Programmable Controllers User Manual 2080-LC20-20QBB Micro820 20-point Programmable Controllers User Manual 2080-LC20-20QWB Micro820 20-point Programmable Controllers User Manual