Rockwell Automation 2080-LC20-20QBBR Micro820 20-point Programmable Controllers User Manual User Manual
Page 126
Appendix B
Troubleshooting
118
Rockwell Automation Publication 2080-UM005A-EN-E - December 2013
0xF860
A data overflow occurred.
A data overflow error is generated when the ladder,
structured text or function block diagram execution
encounters a divide-by-zero.
Perform the following:
•
Correct the program to ensure that there is no data overflow.
•
Build and download the program using Connected Components
Workbench.
•
Put the Micro800 controller into Run mode.
0xF870
An index address was out of data space.
Perform the following:
•
Correct the program to ensure that there is no index address out of data
space.
•
Build and download the program using Connected Components
Workbench.
•
Put the Micro800 controller into Run mode.
0xF880
A data conversion error occurred.
Perform the following:
Correct the program to ensure that there is no data conversion error.
•
Build and download the program using Connected Components
Workbench.
•
Put the Micro800 controller into Run mode.
0xF888
The call stack of the controller cannot support the
sequence of calls to function blocks in the current
project. Too many blocks are within another block.
Change the project to reduce the quantity of blocks being called within a
block.
0xF898
An error occurred in the user interrupt configuration for
the plug-in I/O module.
Correct the user interrupt configuration for plug-in I/O module in the user
program to match that of the actual hardware configuration.
0xF8A0
The TOW parameters are invalid.
Perform the following:
•
Correct the program to ensure that there are no invalid parameters.
•
Build and download the program using Connected Components
Workbench.
•
Put the Micro800 controller into Run mode.
0xF8A1
The DOY parameters are invalid.
Perform the following:
•
Correct the program to ensure that there are no invalid parameters.
•
Build and download the program using Connected Components
Workbench.
•
Put the Micro800 controller into Run mode.
0xFFzz
(Note: zz
indicates the
last byte of the
program
number. Only
program
numbers up to
0xFF can be
displayed. For
program
numbers
01x00 to
0xFFFF, only
the last byte is
displayed.)
A user-created fault from Connected Components
Workbench has occurred.
Contact your local Rockwell Automation technical support representative if
the error persists.
List of Error Codes for Micro800 Controllers
Error Code
Description
Recommended Action
- 2080-LC20-20AWBR Micro820 20-point Programmable Controllers User Manual 2080-LC20-20QWBR Micro820 20-point Programmable Controllers User Manual 2080-LC20-20AWB Micro820 20-point Programmable Controllers User Manual 2080-LC20-20QBB Micro820 20-point Programmable Controllers User Manual 2080-LC20-20QWB Micro820 20-point Programmable Controllers User Manual