Operating the LIST Function

Chapter 4

4Ć15

If this situation occurs you should:

Clear the bad fault address in a fault routine
Clear the block transfer bit
Restart the block transfer in the ladder diagram program

Auto config first creates a new I/O chassis list in which each I/O chassis
has equal priority with no attributes assigned. Then a reconfiguration
executes.

The 1775-S4B scanner performs an auto configure at powerup under the
following conditions:

No I/O channel configured for I/O scan has entries in the rack list.

Neither auto configure nor reconfigure has been selected during a

previous powerup (at least since the last time you cleared memory).

When forming the I/O chassis list during an auto configuration, the
1775-S4B scanner polls all valid addresses (rack 0 to 768). If the
1775-S4B scanner receives response to an address, it adds that I/O rack
address to the list. To assign attributes or priorities to the I/O chassis, add
them manually through LIST and reconfigure the I/O channel.

You can only perform an auto configuration when:

PLC-3 processor is in program load mode.

Power is applied to the I/O chassis.

Switch 2 of each I/O chassis is set to “on” to allow the I/O chassis to be

restarted from the PLC-3 processor.

If power is not applied to the I/O chassis, the PLC-3 processor attempts to
perform an auto configuration, and since the I/O chassis does not respond,
the 1775-S4B scanner does not enter it in the I/O chassis list. For an entry
to get into the I/O chassis list in auto config, a valid communication path
must exist between the 1775-S4B scanner and the I/O adapter module for
the I/O chassis.