Operating the LIST Function
Chapter 4
4Ć11
The bits/char selections are 7 or 8. The channel transmits the selected
number of data bits per character. The channel only accepts characters
received with the selected number of data bits per character. The default
selection is 8 data bits per character.
The ASCII code size selections are 7 or 8. You use this selection when 8
data bits per character is selected. Then select one of the following:
If you select:
Then:
7
8
The RSĆ232ĆC communication channel uses the first 7 bits only
in decoding the character transmitted.
The RSĆ232ĆC communication channel uses all 8 bits in
decoding the character transmitted.
The default ASCII code size is 7.
The reconfigure selection implements the channel 5 selections. For
example, if you select CRT defaults, the 1775-S4B scanner does not
implement the change until you select reconfigure. In response to selecting
reconfig:
If channel 5:
Then:
Is not currently executing
Is currently executing
The 1775ĆS4B scanner reconfigures the channel immediately.
The 1775ĆS4B scanner waits until the task completes executing
before it reconfigures the channel.
When the 1775-S4B scanner reconfigures the channel, the asterisk beside
the reconfiguration selection disappears.
If you select I/O CHAN to configure an I/O communication channel, you
can select the following parameters:
I/O Chan 1
I/O Chan 2
I/O Chan 3
I/O Chan 4
Racks
Auto
Config
Reconfig
We explain these parameters in the following sections.
4.2.14
Data Bits Per Character
4.2.15
ASCII Code Size
4.2.16
Reconfigure
4.3
Configuring the I/O
Communication Channels