Page 21

background image

Installing Your 1775ĆS4B Scanner

Chapter 3

3Ć7

Figure 3.7

I/O Adapter Module (cat. no. 1771ĆAS) Terminal Identification Label

1

2

3

4

5

6

7

8

9

10

11

12

Line 1

Line 2

Shield

No connection

IN

RET

Reset

Cable

No connection

No connection

No connection

No connection

No connection

No connection

Terminal

Identification

Cat. No. 1771ĆAS

Perform the following steps to make proper I/O channel connections:

Step 1—Connect the twinaxial cable in a serial (daisy chain) fashion from
the 1775-S4B scanner to each I/O chassis within the I/O channel
(figure 3.8).

Step 2—Connect the signal conductor with blue insulation to the LINE 1
terminal at the 1775-S4B scanner and at each I/O adapter module in the
I/O channel.

Step 3—Connect the signal conductor with clear insulation to the LINE 2
terminal. Connect the shield drain wire to the SHIELD terminal.

Step 4—Connect a Terminator (cat. no. 1770-XT) between the terminals at
each end of each I/O channel.

You can optionally connect a normally open, momentary contact switch
between terminals 11 and 12 at each I/O adapter module. You could then
use such a reset switch to reset the I/O adapter module if the PLC-3
processor detects a fault at the I/O chassis. Refer to the PLC-3
Programmable Controller Installation and Operation Manual (publication
1775-6.7.1, formerly 1775-800) for detailed information.