beautypg.com

12 - execution time considerations, 12ć1, Execution time considerations – Rockwell Automation 1775-S4B,D17756.5.3 User Manual SCANNER/MSG HND User Manual

Page 132

background image

Chapter

12

12Ć1

Execution Time Considerations

After reading this chapter, you will be aware of the factors that affect
1775-S4B scanner execution time.

The 1775-S4B scanner can execute procedures of many commands,
operators, and functions. However, each command, operator, and function
takes a certain amount of time to execute. In some cases, a procedure
executes faster than the data transmits for printing. In other cases, the
execution time may be long enough to cause a delay between print items in
a procedure.

Obviously, one factor in execution time is the length of a procedure; the
longer the procedure, the longer the execution time. However, you should
also consider the following less obvious factors:

Active I/O channels
Address

complexity

Symbol

order

Assignment

values

Command line comments

We describe these factors in the following five sections.

The 1775-S4B scanner gives top priority to its four I/O channels. If any
I/O channels are active, the 1775-S4B scanner gives top priority to
scanning and processing I/O data.

You should also be aware that it takes several times longer to execute a
procedure while four I/O channels are active than while no I/O channels
are active.

If procedure execution speed is critical in your application, you can make
the unused I/O channels inactive in LIST to increase speed. Refer to
chapter 4 for detailed information on the LIST function.

You also might consider adding another 1775-S4A scanner to perform I/O
scans. This additional scanner could enable the 1775-S4B scanner to
execute procedures with all its I/O channels inactive.

12.0
Chapter Objectives

12.1
Introduction

12.2
Active I/O Channels