beautypg.com

Rockwell Automation 1772-LS_LSP,D17726.8.6 PROG/OPER MANUAL-MINI PLC-2/05 User Manual

Page 31

background image

Hardware

Chapter 3

3-5

Fuse
Purpose: Guards against overcurrent conditions on the input line.

Sizes: 1.0 amp fuse for 120V AC operations

Terminal Strip
Purpose: To provide wire connections for the processor.

Hardware: Terminals L1, N and GND label the AC input connections.

Switch Assembly on the I/O Chassis
Purpose: Determines processor response to memory protect and
power-up sequence.

Location: Left side of the I/O chassis backplane.

Settings:

If

Then

Switch 8 is on

Memory protection is on. Memory above 20

08

cannot be changed by

the programmer.

Switch 8 is off

Memory protection is disabled. memory can be changed by the

programmer. Memory can be changed when the processor module is

in the program mode.

Switch 6 is off

Contents of the EEPROM is always transferred to the CMOS RAM at

powerĆup.

Switch 6 is on

and

Switch 7 is off

Memory transfer does not occur and the module gives a fault

indication.

Switch 6 is on

and

Switch 7 is on

If the CMOS RAM passes its checksum on powerĆup, the contents of

the EEPROM transfer to the CMOS RAM.

The settings for Switch 1- Switch 5 do not matter.

Important: Series A/Revision A of the 1770-T3 industrial terminal is not
compatible with memory protect feature.

ATTENTION: Use a ball point pen to set each switch. Do not
use a lead pencil because the tip can break off and jam
the switch.