Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual
Page 99
Using the I/O
5-25
20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P
Understanding PLC-5 Controller Data Table Addresses
Because the PLC-5 controller is a 16-bit platform and is used with the
32-bit 20-COMM-C or 20-COMM-Q adapter, the data will be transposed
from the least-significant word (LSW) to the most-significant word (MSW)
in the controller.
When the I/O was configured (
), two available data table
addresses (N9:0 for input data and N10:0 for output data) were used.
shows the data file address structure for this example.
Figure 5.12 Data File Table for Example Ladder Logic Program
Depending on the drive,
Table 5.J
,
Table 5.K
,
Table 5.L
,
Table 5.M
,
, or
show the I/O definitions as they relate to the N9:0
and N10:0 data table addresses in
being used in this example.
TIP: When using a drive that has 16-bit Datalinks (PowerFlex 70,
PowerFlex 700, and PowerFlex 700H drives) to transfer a 32-bit parameter,
two contiguous drive Datalink parameters (for example, Data Out A1/A2,
B1/B2, and so forth) are required. To determine if a parameter is a 32-bit
parameter, see the Parameter section in the drive documentation and look
for a
symbol in the ‘No.’ column. (All parameters in PowerFlex 700
Series B drives are 32-bit parameters.) For example, parameter 3 - [Output
Current] in a PowerFlex 70 EC drive is a 32-bit parameter. When using a
drive that has 32-bit Datalinks (PowerFlex 700 VC, PowerFlex 700S, and
PowerFlex 750-Series drives), only one drive Datalink parameter is required
to transfer any parameter.
32