B-4
Adapter Parameters
20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P
25
[M-S Input]
Sets the Master-Slave input data. This data is
produced by the scanner and consumed by the
adapter.
Default:
xxx0 0001
Bit Values:
0 = I/O Disabled
1 = I/O Enabled
Type:
Read/Write
Reset Required: Yes
26
[M-S Output]
Sets the Master-Slave output data. This data is
produced by the adapter and consumed by the
Master device (for example, scanner).
Default:
xxx0 0001
Bit Values:
0 = I/O Disabled
1 = I/O Enabled
Type:
Read/Write
Reset Required: Yes
27
[Ref Adjust]
Sets the percent scale factor for the Reference
received from the network.
Default:
100.00%
Minimum:
0.00%
Maximum:
200.00%
Type:
Read/Write
Reset Required: No
Parameter
No.
Name and Description
Details
Bit
Definition
Not
Used
Not
Used
Not
Used
Dat
a
link D
In
put
Dat
a
link C
In
put
Data
link B
Inpu
t
Data
link A
Inpu
t
Cmd/Ref
Default
x
x
x
0
0
0
0
1
Bit
7
6
5
4
3
2
1
0
Bit
Definition
Not Used
Not Used
Not Used
Datalink D
O
ut
put
Datalink C
O
ut
put
Dat
alink B Out
put
Dat
alink A Out
put
Cmd/
Ref
Default
x
x
x
0
0
0
0
1
Bit
7
6
5
4
3
2
1
0
!
ATTENTION: To guard against equipment damage and/or personal injury, note
that changes to Parameter 27 - [Ref Adjust] take effect immediately. A drive
receiving its Reference from the adapter will receive the newly scaled
Reference, resulting in a change of speed.