4-34

Configuring the I/O

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

h. Reboot the computer and repeat steps 1 through 7 at the beginning

of this subsection.

The Unrecognized Device icon in the RSNetWorx for ControlNet
graph view window in step 7 should have been replaced by a drive
icon (for this example, the icon for a PowerFlex 70 EC drive).

8. Select Network > Enable Edits or check the Edits Enabled box in the

RSNetWorx for ControlNet project window.

If the 1747-SCNR scanner has a different I/O configuration than the
configuration now being saved, the Online/Offline mismatch dialog box
will appear.

a. When both Options choices are available, click ‘Use offline data

(download)’. When this choice is dimmed (grayed out), you must
click ‘Use online data (upload)’.

b. Click OK.

9. In the RSNetWorx for ControlNet graph view window, right-click the

1747-SCNR icon and choose Scanlist Configuration to display the
Scanlist Configuration screen.

TIP: If a message box reports that the download cannot be
completed because the controller is not in Program mode, click
Change Mode to place the controller in Remote Run mode and
continue the download.