Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual
Page 117
Using the I/O
5-43
20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P
PowerFlex 700 Drives with Vector Control and PowerFlex 700L Drives with 700
Control
When using any of these drives, which contain DINT (32-bit format) data
types, you will read from and write to the LSW data table address in the
controller.
Table 5.S SLC 500 Data Table Addresses for:
PowerFlex 700 Drives with Vector Control
PowerFlex 700L Drives with 700 Control
Data Table Address Description
N9:0
Reserved for scanner status
N9:1
Reserved for scanner status
N9:2
N9:3
Speed Feedback
N9:4
Value of parameter assigned to Parameter 310 [Data Out A1] LSW
N9:5
Value of parameter assigned to Parameter 310 [Data Out A1] MSW
N9:6
Value of parameter assigned to Parameter 311 [Data Out A2] LSW
N9:7
Value of parameter assigned to Parameter 311 [Data Out A2] MSW
N9:8
Value of parameter assigned to Parameter 312 [Data Out B1] LSW
N9:9
Value of parameter assigned to Parameter 312 [Data Out B1] MSW
N9:10
Value of parameter assigned to Parameter 313 [Data Out B2] LSW
N9:11
Value of parameter assigned to Parameter 313 [Data Out B2] MSW
N9:12
Value of parameter assigned to Parameter 314 [Data Out C1] LSW
N9:13
Value of parameter assigned to Parameter 314 [Data Out C1] MSW
N9:14
Value of parameter assigned to Parameter 315 [Data Out C2] LSW
N9:15
Value of parameter assigned to Parameter 315 [Data Out C2] MSW
N9:16
Value of parameter assigned to Parameter 316 [Data Out D1] LSW
N9:17
Value of parameter assigned to Parameter 316 [Data Out D1] MSW
N9:18
Value of parameter assigned to Parameter 317 [Data Out D2] LSW
N9:19
Value of parameter assigned to Parameter 317 [Data Out D2] MSW
N10:0
Logic Command (see
N10:1
Speed Reference
N10:2
Value of parameter assigned to Parameter 300 [Data In A1] LSW
N10:3
Value of parameter assigned to Parameter 300 [Data In A1] MSW
N10:4
Value of parameter assigned to Parameter 301 [Data In A2] LSW
N10:5
Value of parameter assigned to Parameter 301 [Data In A2] MSW
N10:6
Value of parameter assigned to Parameter 302 [Data In B1] LSW
N10:7
Value of parameter assigned to Parameter 302 [Data In B1] MSW
N10:8
Value of parameter assigned to Parameter 303 [Data In B2] LSW
N10:9
Value of parameter assigned to Parameter 303 [Data In B2] MSW
N10:10
Value of parameter assigned to Parameter 304 [Data In C1] LSW
N10:11
Value of parameter assigned to Parameter 304 [Data In C1] MSW
N10:12
Value of parameter assigned to Parameter 305 [Data In C2] LSW
N10:13
Value of parameter assigned to Parameter 305 [Data In C2] MSW
N10:14
Value of parameter assigned to Parameter 306 [Data In D1] LSW
N10:15
Value of parameter assigned to Parameter 306 [Data In D1] MSW
N10:16
Value of parameter assigned to Parameter 307 [Data In D2] LSW
N10:17
Value of parameter assigned to Parameter 307 [Data In D2] MSW