Host dpi parameter object, Class code, Instances – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual
Page 240: Class attributes, Host dpi parameter, Host dpi, Clas, C-30
C-30
ControlNet Objects
20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P
Host DPI Parameter Object
Class Code
To access ‘Device’ parameters, use the DPI Parameter Object (Class Code
0x93).
Important: The Host DPI Parameter Object is supported only when the
adapter is used with a PowerFlex 750-Series drive.
Instances
The number of instances depends on the number of parameters in the device.
The total number of parameters can be read in Instance 0, Attribute 0.
Class Attributes
Hexadecimal
Decimal
0x9F
159
Instances (Hex.)
(Dec.)
Device
Example Description
0x0000…0x3FFF
0…16383
Reserved
16384
Class Attributes (Adapter)
0x4000…0x43FF
16384…17407
Adapter
16385
Adapter Parameter 1 Attributes
0x4400…0x47FF
17408…18431
DPI Port 1
16386
Adapter Parameter 2 Attributes
0x4800…0x4BFF
18432…19455
DPI Port 2
…
…
0x4C00…0x4FFF 19456…20479
DPI Port 3
17408
Class Attributes (HIM)
0x5000…0x53FF
20480…21503
DPI Port 4
17409
HIM Parameter 1 Attributes
0x5400…0x57FF
21504…22527
DPI Port 5
17410
HIM Parameter 2 Attributes
0x5800…0x5BFF
22528…23551
DPI Port 6
…
…
0x5C00…0x5FFF 23552…24575
DPI Port 7
0x6000…0x63FF
24576…25599
DPI Port 8
0x6400…0x67FF
25600…26623
DPI Port 9
0x6800…0x6BFF
26624…27647
DPI Port 10
0x6C00…0x6FFF 27648…28671
DPI Port 11
0x7000…0x73FF
28672…29695
DPI Port 12
0x7400…0x77FF
29696…30719
DPI Port 13
0x7800…0x7BFF
30720…31743
DPI Port 14
Attribute ID
Access Rule Name
Data Type
Description
0
Get
Number of Instances
WORD
Number of parameters in the device
1
Set
Write Protect Password
WORD
0 = Password disabled
n = Password
2
Set
NVS Command Write
BYTE
0 = No Operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory
3
Get
NVS Parameter Value Checksum
WORD
Checksum of all parameter values in a user set in NVS
4
Get
NVS Link Value Checksum
WORD
Checksum of parameter links in a user set in NVS
5
Get
First Accessible Parameter
WORD
First parameter available if parameters are protected by
passwords. A ‘0’ indicates all parameters are protected.
7
Get
Class Revision
WORD
2 = DPI
8
Get
First Parameter Processing Error
WORD
The first parameter that has been written with a value
outside of its range. A ‘0’ indicates no errors.
9
Set
Link Command
BYTE
0 = No Operation
1 = Clear All Parameter Links (This does not clear links
to function blocks.)