beautypg.com

I/o board option (20-xcomm-io-opt1), Understanding the i/o image (drive + i/o option) – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 202

background image

8-2

Using the Adapter in a DPI External Comms Kit (20-XCOMM-DC-BASE)

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

I/O Board Option
(20-XCOMM-IO-OPT1)

The I/O Board option, when installed in the DPI External Comms Kit, can
be used with only a Series B adapter, firmware revision 3.xxx or later. The
I/O Board provides six DC inputs and two Relay outputs for use by a
controller on the network.

Figure 8.2

I/O Connector Function Descriptions

For more information, see the I/O Board Option Installation Instructions,
publication 20COMM-IN002.

Understanding the I/O Image
(Drive + I/O Option)

The data for the optional I/O Board is sent over the I/O connection using
Datalink D. When the optional I/O Board is installed in the DPI External
Comms Kit, Datalink D is dedicated only for this function and is not
available for other uses. When the adapter detects the presence of the
optional I/O Board, the I/O image is modified as shown in

Figure 8.3

.

Figure 8.3

Example I/O Image - Datalink D Dedicated to I/O Board and All I/O Enabled

O2 - NO

O2 - COM

O1 - NC

O1 - NO

O1 - COM

IN1

IN2

IN3

IN4

IN5

IN6

INPUT COM

OUT2

OUT1

3 4

5

6

2

1

9 10 11 12

8

7

Controller

Scanner

Adapter Word and I/O

ControlNet

Message

Handler

0 Logic Command
1 Reference
2 Datalink In A1
3 Datalink In A2
4 Datalink In B1
5 Datalink In B2
6 Datalink In C1
7 Datalink In C2
8 Datalink In D1
9 Datalink In D2

Output

Image

(Write)

0 Pad Word

(1)

1 Pad Word

(1)

2 Logic Status
3 Feedback
4 Datalink Out A1
5 Datalink Out A2
6 Datalink Out B1
7 Datalink Out B2
8 Datalink Out C1
9 Datalink Out C2
10 Datalink Out D1
11 Datalink Out D2

Input

Image

(Read)

Message

Buffer

Logic Command
Reference
Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
Data In D2

Logic Status
Feedback
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2
Data Out D1
Data Out D2

Message

Handler

PowerFlex Drive

DPI

Opt. I/O

Board

(Outputs)

Opt. I/O

Board

(Inputs)

(1)

Required by ControlLogix when using the Generic Profile. May or may not be required by other types of controllers.