Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual
Page 189
Using Explicit Messaging
6-61
20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P
SLC 500 Controller Example Scattered Write Request Data
In this message example, we use the data table addresses in
Figure 6.77
or
Figure 6.80
to store the request values to be written to these drive
parameters.
See
DPI Parameter Object on page C-16
(Class code 0x93) or
(Class code 0x9F) for parameter
numbering.
Figure 6.77
or
Figure 6.80
shows the parameter values.
Figure 6.77 Example Scattered Write Request Data File for PowerFlex 7-Class Drive
SLC 500 Controller Example Scattered Write Response Data
In this message example, we use the data table addresses in
Figure 6.78
to
store the response values that were written to the requested drive
parameters. Values of ‘0’ indicate no errors occurred.
Figure 6.78 Example Scattered Write Response Data File for PowerFlex 7-Class Drive
The PowerFlex 750-Series drive uses 32-bit integer and REAL parameters.
A COP command must be used to copy the 16-bit integer or REAL values
to the N90 integer array.
Figure 6.79
shows the ladder logic used for this
example. If the parameter data type is a 32-bit integer, the data remains split
into two 16-bit integers since there are no 32-bit integers in the SLC 500
PowerFlex 7-Class
Drive Parameter
Address
Write Value
PowerFlex 750-Series
Drive Parameter
Write Value
Data Type
141 - [Accel Time 2]
N90:1
11.1 Sec.
536 - [Accel Time 2]
11.1 Sec.
REAL
143 - [Decel Time 2]
N90:4
22.2 Sec.
538 - [Decel Time 2]
22.2 Sec.
REAL
105 - [Preset Speed 5]
N90:7
33.3 Hz.
725 - [Zero Position]
33
32-bit integer
106 - [Preset Speed 6]
N90:10
44.4 Hz.
21555 - [Port 5: Analog In0 Hi]
5.5
REAL
107 - [Preset Speed 7]
N90:13
55.5 Hz.
780 - [PTP Setpoint]
-75,555
32-bit integer