3-4
Configuring the Adapter
20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P
4. If you enabled one or more Datalinks, configure parameters in the drive
to determine the source and destination of data in the Datalinks.
When using Datalinks, up to 8 drive [Data In xx] parameters
(300…307) and/or up to 8 [Data Out xx] parameters (310…317) must
be assigned to point to the appropriate drive parameters for your
application. See
for an example.
5. Reset the adapter (see
Resetting the Adapter on page 3-7
).
The adapter is ready to receive I/O. You must now configure the adapter to
receive I/O from the master. See
Setting Master-Slave Hierarchy
Setting Master-Slave
Hierarchy
A hierarchy determines the type of device with which the adapter exchanges
data. In a Master-Slave hierarchy, the adapter exchanges data with a master,
such as a bridge or scanner (1756-CNB/CNBR, 1747-SCNR, and so forth).
1. Enable the desired I/O in Parameter 13 - [DPI I/O Cfg].
See
Setting the I/O Configuration on page 3-3
2. Set the bits in Parameter 25 - [M-S Input].
This parameter determines the data received from the master by the
drive. A ‘1’ enables the I/O and a ‘0’ disables the I/O.
Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.
3. Set the bits in Parameter 26 - [M-S Output].
This parameter determines the data transmitted from the drive to the
bridge or scanner. A ‘1’ enables the I/O and a ‘0’ disables the I/O.
Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.
4. Reset the adapter (see
Resetting the Adapter on page 3-7
).
Bit
Description
0
Logic Command/Reference (Default)
1
Datalink A Input
2
Datalink B Input
3
Datalink C Input
4
Datalink D Input
5…15
Not Used
Port 5 Device
20-COMM-C
Parameter #: 25
M-S Input
x x x x x x x x x x x 0 0 0 0
1
Cmd/Ref
b00
Bit
Description
0
Status/Feedback (Default)
1
Datalink A Output
2
Datalink B Output
3
Datalink C Output
4
Datalink D Output
5…15
Not Used
Port 5 Device
20-COMM-C
Parameter #: 26
M-S Output
x x x x x x x x x x x 0 0 0 0
1
Status/Fdbk
b00