Using Explicit Messaging

6-53

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

SLC 500 Controller – Explanation of Request and Response Data for
Read/Write Multiple Messaging

The data structures in

Figure 6.66

and

Figure 6.67

use 16-bit words and can

accommodate up to 22 parameters in a single message. In the Response
Message, a parameter number with the high bit set indicates that the
associated parameter value field contains an error code (parameter number
in response data will be negative).

Important: See

Table 6.A on page 6-2

for limitations of PowerFlex 7-Class

and PowerFlex 750-Series drives when using Class code 0x93
or Class code 0x9F for explicit messaging.

Figure 6.66 Data Structures for Scattered Read Messages

Figure 6.67 Data Structures for Scattered Write Messages

Request (Source Data)

Response (Destination Data)

Word 0 Parameter Number

Word 0 Parameter Number

1 Pad Word

1 Parameter Value LSW

2 Pad Word

2 Parameter Value MSW

3 Parameter Number

3 Parameter Number

4 Pad Word

4 Parameter Value LSW

5 Pad Word

5 Parameter Value MSW

6 Parameter Number

6 Parameter Number

7 Pad Word

7 Parameter Value LSW

8 Pad Word

8 Parameter Value MSW

9 Parameter Number

9 Parameter Number

10 Pad Word

10 Parameter Value LSW

11 Pad Word

11 Parameter Value MSW

12 Parameter Number

12 Parameter Number

13 Pad Word

13 Parameter Value LSW

14 Pad Word

14 Parameter Value MSW

...

...

63 Parameter Number

63 Parameter Number

64 Pad Word

64 Parameter Value LSW

65 Pad Word

65 Parameter Value MSW

Request (Source Data)

Response (Destination Data)

Word 0 Parameter Number

Word 0 Parameter Number

1 Parameter Value LSW

1 Pad Word

2 Parameter Value MSW

2 Pad Word

3 Parameter Number

3 Parameter Number

4 Parameter Value LSW

4 Pad Word

5 Parameter Value MSW

5 Pad Word

6 Parameter Number

6 Parameter Number

7 Parameter Value LSW

7 Pad Word

8 Parameter Value MSW

8 Pad Word

9 Parameter Number

9 Parameter Number

10 Parameter Value LSW

10 Pad Word

11 Parameter Value MSW

11 Pad Word

12 Parameter Number

12 Parameter Number

13 Parameter Value LSW

13 Pad Word

14 Parameter Value MSW

14 Pad Word

...

...

63 Parameter Number

63 Parameter Number

64 Parameter Value LSW

64 Pad Word

65 Parameter Value MSW

65 Pad Word